Avoiding bad smells in the bathroom

Anthony Cam asks:
Does anyone have a problem with internal venting? I have used an air admittance valve on my soil stack which has worked fine for the three months since we moved in but we now seem to have smells emanating from the wet floor drain in the shower/toilet and, more recently, from the washbasin in the bathroom. Would an open-vented stack fix this?

Mark reckons:

The probable cause of your problem is the failure of the water traps in your shower and your basin. However, to pinpoint the reason for this is difficult. There are several reasons why water traps fail.

The commonest one is due to something called 'induced siphonage': this occurs when the water in the traps gets sucked down the waste pipes by pressure created by stuff happening elsewhere in the waste system.

Why should this happen in some systems and not in others?

There are a number of identified causes: the waste pipes maybe the wrong size for the appliance, or the individual runs are the wrong length or laid at the wrong fall, or the jointing with the soil stack may be too close to other connections. The best practice notes for what should happen, in an ideal world, in order to avoid these problems are all set out in Part H1 of the E&W building regs, but these are often ignored (they rarely get inspected) and are sometimes just impractical to install in any event.

If the water traps fail, then there is an obvious danger that drain smells will start entering the bathroom. The vented soil stack is a designed as a failsafe in event of the water traps failing: the bad smells will usually take the route of least resistance, being straight up the stack and out through the roof. An air admittance valve (AAV), used more and more widely these days in place of vented soil stacks, does not provide nearly such a good escape path for bad smells; they only open when there is a significant pressure imbalance between the waste pipes and the surrounding house. If your waste traps have failed, the bad smells will be far more likely to seep out through your plugholes than through your AAV, as your traps have now become open pathways for the foul air.

What to do about it? One potential solution might be to replace the AAV sitting at the top of your stack with a full height, open-vented stack, exiting through the roof: it might just do the trick, but it might not. If that doesn't sort it, then you then have to re-plumb the waste runs.

If you do, then consider replacing the existing traps with Hepworth HepVO valves (pictured above and pronounced Hep Vee-Oh), a patented non-return valve which has been on the market since 1997. The HepVO valve system is engagingly simple to understand. There are only three components; the valve itself which looks pretty much like any other piece of pushfit plastic pipe fitting, a straight connector and a knuckle or bend, each available in two sizes (32mmm for basins, 40mm for baths). The innovation is inside the valve where a one-way membrane is stretched across the walls: this allows water and air to pass through it downstream into the waste pipes but stops foul air passing upstream into the house. They are widely available from plumber's merchants (though they sellremarkablyy few, it seems) at a cost of between £12 and £15 a time.

Earlier this year, the BRE (Building Research Establishment, the UK's premier building research body) published an assessment of the product. It was remarkably positive about the valve in almost all applications you could think of using it but one conclusion was particularly interesting: it suggested that when you use two or more HepVO valves in a top floor bathroom, you no longer require either an open-vented soil stack or an AAV stub-stack arrangement.

So if you can get access to the traps that are defective, I would have thought replacing them with HepVO valves would be a very good move.


Self-sealing waste valves for domestic use: an assessment BRE Paper IP5/05 by White, Griggs and Sutcliffe. Mark Brinkley

If you can only see this single article on screen please click on the 'Housebuilder's Update' heading (screen top left) to view the rest of this month's items and have access to our archives.

Labels:

2 Comments:

Anonymous Tim said...

This article is excellent - thanks, it solved my problem... for about 2 weeks then the smell came back. It no longer can be smelt from plug-holes, but it seems to be coming from the toilet, perhaps under the rim. I have cleaned and cleaned everything, but bad air still seems to be getting in. Any suggestions would be very well recieved. Thanks Tim

11:36 am  
Anonymous glen lord said...

An over sensitive nose. if the smell is above the rim then its is not from the drainage system unless you can prove that the trap on the loo is being drawn. the exception to this could be an old siphonic flush toilet if the aspirator rubber is perished and scale has built up in the 2nd trap causing self siphoning. does any one else in the home smell the smells?

7:35 pm  